Florida · city · ERRCS / BDA requirements

ERRCS and BDA requirements in St. Petersburg, Florida

St. Petersburg Fire Rescue's fire marshal is the AHJ in the city. Pinellas County Resolution No. 23-24 binds every fire department in the county, so St. Petersburg high-rises must keep -102 dBm with DAQ 3.4. The city uses the county's 800 MHz system, and the county is the license holder.

Last verified Updated Confidence medium5 sourcesChangelog

Waterfront mid-rise buildings on a Gulf-coast bay.

Confidence medium

Last verified

Check this building

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with St. Petersburg Fire Rescue, Fire Marshal before you design, permit or test a system.

Who must comply

State rules apply here too. See Florida statewide rules.

RuleEffectCitationSource
New and existing high-rise buildings must maintain at least -102 dBm with DAQ 3.4 or better in all critical and non-critical areas.Must meetPinellas County Resolution No. 23-24Pinellas County Safety and Emergency Services
TriggerPublished value
Minimum building sizeNot published; confirm with the fire marshal
Minimum storiesNot published; confirm with the fire marshal
Height triggerNot published; confirm with the fire marshal
Below-grade areasNot published; confirm with the fire marshal
Building types namedNot published; confirm with the fire marshal
Existing buildings must retrofitYes
Compliance deadlineNot published; confirm with the fire marshal

The city's own fire rescue site does not publish BDA guidance; the requirements below come from Pinellas County.

questions, about a minute

Free. Runs in your browser; nothing is sent until you ask for quotes. The full checker asks a few more questions.

RequirementValue
Minimum downlink signal-102 dBm
Minimum uplink signalNot published; confirm with the fire marshal
Delivered audio quality (DAQ)3.4
Coverage, general areasNot published; confirm with the fire marshal
Coverage, critical areasNot published; confirm with the fire marshal
Critical areas namedNot published; confirm with the fire marshal
Public safety radio bands800 MHz SmartZone (Pinellas County system, used by the City of St. Petersburg)

From the county resolution; no coverage percentage is stated.

A condominium parking garage with concrete columns and a ramp.
Below-grade garages are where outside radio signal fades first.

How coverage is tested

One floor, 20 squares, a radio check in each

Illustration
The coverage test grid on one floorA floor plan divided into 20 equal test areas in a 5 by 4 grid, with a test spot at the center of each. The stair and the elevator lobby are marked as critical areas. Nineteen areas pass and one fails, so this floor passes.StairElevators1234
  1. 20 test areas per floorEach floor is divided into a grid of 20 roughly equal areas.IFC 2021 510.5.4
  2. One test spot per areaA spot near the center stands for the whole area. No extra spots after it is chosen.
  3. One failed area is allowedMore than one failed area fails the floor. With exactly two, the floor may be re-divided into 40 areas, and up to two non-adjacent failures are allowed.IFC 2021 510.5.4
  4. Critical areas count moreTypical model-code targets: 95 percent of all areas and 99 percent of critical areas such as stairs and elevator lobbies. Your fire marshal sets the numbers that apply to you.IFC 2021 510.4.1

Illustration: 19 of 20 areas pass, so this floor passes. Some fire departments use other numbers; Miami-Dade, for example, stops an acceptance test below 90 percent of general areas.

How the model fire code's grid test decides whether a floor has enough radio coverage.Source: IFC 2021 510.4.1, 510.5.4. Typical model-code values; your AHJ sets them.

Testing

TestWhat the source saysSource
Acceptance testProvisional county retransmission authorization covers activation, optimization and testing; final authorization follows commissioning and is valid for five years.Resolution No. 23-24
Annual testNot published in the local documents we found; confirm with the fire marshal.None found
Five-year testNot published in the local documents we found; confirm with the fire marshal.None found
Coverage assessment intervalSet by state law: the fire marshal may require an interior coverage assessment no more than once every 3 years for an existing high-rise or an existing building over 12,000 total gross square feet, and once every 5 years for other existing buildings, with exceptions for major alterations, reported radio failures and imminent threats.F.S. 633.202(18)(c)2
A firefighter keys a shoulder microphone in a stairwell.
Testers check talk-in and talk-out from stairwells and other critical areas.

Permit and inspection process

  1. Have a qualified vendor run a grid test coordinated with the county radio section, and send results to the city fire marshal and [email protected]. Pinellas BDA FAQ
  2. Submit plans through St. Petersburg Fire Rescue plans review and the city's building permitting. Plans Review page
A technician sets up a signal meter in a corridor.
A signal survey comes before any design or permit.

Your notice

How long do we have?

Every date here comes from the statute or rule cited under it.

In Florida, after the fire marshal issues a notice of code violation, the owner gets at least 1 year to complete a required retrofit. The date written on your notice controls; it may give you more. F.S. 633.202(18)(g)

Codes and standards referenced

Code or standardEditionSource
Florida Fire Prevention Code (NFPA 1 and NFPA 101, Florida editions), in force statewide8th edition (NFPA 1, Florida 2021 edition), effective December 31, 2023rule
Pinellas County Resolution No. 23-24 (2023), which applies to all fire departments in the county2023pin

Next step

Take the board a plan, not just a problem

Ask for up to 3 quotes from vetted installers who serve your area, or start with a one-page brief the board can read before the next meeting. Free for owners, boards and managers. No texts, no cold calls.

Questions people ask

Does the Pinellas County signal rule apply inside St. Petersburg?

Yes. Resolution No. 23-24 applies to all fire departments enforcing fire codes in incorporated or unincorporated Pinellas County.

Who issues permission to rebroadcast the radio system?

Pinellas County Safety and Emergency Services, the FCC license holder for the 800 MHz system St. Petersburg uses.

Sources

Primary documents we read for this page. Rules change; confirm with your fire marshal (AHJ).

  1. Florida Statutes 2026, section 633.202, subsection (18), The Florida SenateVerified October 25, 2026 · statute
  2. Florida Fire Prevention Code, 8th edition: Florida amendments to NFPA 1 (2021 edition), sections 11.10.2 and 11.10.2.1, Florida Division of State Fire MarshalVerified October 25, 2026 · code
  3. Rule 69A-60.003, F.A.C.: NFPA 1, the Fire Code, Florida 2021 edition, adopted (effective 12/31/2023), Florida Department of State, Florida Administrative CodeVerified October 25, 2026 · rule
  4. Plans Review and commercial services, St. Petersburg Fire RescueVerified October 25, 2026 · ahj page
  5. Radio and Technology: Bi-Directional Amplifiers (BDA) FAQ, quoting Pinellas County Resolution No. 23-24, Pinellas County Safety and Emergency ServicesVerified October 25, 2026 · ahj page
Get up to 3 quotesCheck this building