Florida · city · ERRCS / BDA requirements

ERRCS and BDA requirements in Hollywood, Florida

Hollywood Fire Rescue is the fire AHJ in the city. It has not published its own BDA signal levels or test forms that we could find, so the state rules and Broward County's Section 118 permit steps are the published baseline.

Last verified Updated Confidence low6 sourcesChangelog

Mid-rise condominiums along a waterway with boats.

Confidence low

Last verified

Check this building

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with Hollywood Fire Rescue and Beach Safety, Division of Fire Prevention and Life Safety before you design, permit or test a system.

Who must comply

State rules apply here too. See Florida statewide rules.

RuleEffectCitationSource
As in all of Broward, the FCC license holder must approve the plans before review, and the system may not be switched on before the license holder authorizes it.NoteFBC Broward County Edition 118.4Broward County Board of Rules and Appeals
TriggerPublished value
Minimum building sizeNot published; confirm with the fire marshal
Minimum storiesNot published; confirm with the fire marshal
Height triggerNot published; confirm with the fire marshal
Below-grade areasNot published; confirm with the fire marshal
Building types namedNot published; confirm with the fire marshal
Existing buildings must retrofitNot published; confirm with the fire marshal
Compliance deadlineNot published; confirm with the fire marshal

A November 2025 Sun-Sentinel report counted 18 of Hollywood's 83 high-rises cited for weak radio coverage.

questions, about a minute

Free. Runs in your browser; nothing is sent until you ask for quotes. The full checker asks a few more questions.

Signal and coverage

Not published by the city.

RequirementValue
Minimum downlink signalNot published; confirm with the fire marshal
Minimum uplink signalNot published; confirm with the fire marshal
Delivered audio quality (DAQ)Not published; confirm with the fire marshal
Coverage, general areasNot published; confirm with the fire marshal
Coverage, critical areasNot published; confirm with the fire marshal
Critical areas namedNot published; confirm with the fire marshal
Public safety radio bandsNot published; confirm with the fire marshal

Not published by the city. Broward County's guideline values are on the Broward County page; ask Fire Prevention which levels it tests to.

A condominium parking garage with concrete columns and a ramp.
Below-grade garages are where outside radio signal fades first.

How coverage is tested

One floor, 20 squares, a radio check in each

Illustration
The coverage test grid on one floorA floor plan divided into 20 equal test areas in a 5 by 4 grid, with a test spot at the center of each. The stair and the elevator lobby are marked as critical areas. Nineteen areas pass and one fails, so this floor passes.StairElevators1234
  1. 20 test areas per floorEach floor is divided into a grid of 20 roughly equal areas.IFC 2021 510.5.4
  2. One test spot per areaA spot near the center stands for the whole area. No extra spots after it is chosen.
  3. One failed area is allowedMore than one failed area fails the floor. With exactly two, the floor may be re-divided into 40 areas, and up to two non-adjacent failures are allowed.IFC 2021 510.5.4
  4. Critical areas count moreTypical model-code targets: 95 percent of all areas and 99 percent of critical areas such as stairs and elevator lobbies. Your fire marshal sets the numbers that apply to you.IFC 2021 510.4.1

Illustration: 19 of 20 areas pass, so this floor passes. Some fire departments use other numbers; Miami-Dade, for example, stops an acceptance test below 90 percent of general areas.

How the model fire code's grid test decides whether a floor has enough radio coverage.Source: IFC 2021 510.4.1, 510.5.4. Typical model-code values; your AHJ sets them.

Testing

TestWhat the source saysSource
Acceptance testNot published in the local documents we found; confirm with the fire marshal.None found
Annual testNot published by the city. Broward County's annual test rule is on the Broward County page; confirm with the fire marshal.None found
Five-year testNot published in the local documents we found; confirm with the fire marshal.None found
Coverage assessment intervalSet by state law: the fire marshal may require an interior coverage assessment no more than once every 3 years for an existing high-rise or an existing building over 12,000 total gross square feet, and once every 5 years for other existing buildings, with exceptions for major alterations, reported radio failures and imminent threats.F.S. 633.202(18)(c)2
A firefighter keys a shoulder microphone in a stairwell.
Testers check talk-in and talk-out from stairwells and other critical areas.

Permit and inspection process

  1. Ask Fire Prevention and Life Safety (954.967.4404) how to request a radio signal test for your building. City inspections page
  2. If a system is needed, follow Broward's Section 118 process: engineer-sealed design, license holder approval, then city building, electrical and fire permits. BORA Guidelines 1.4 to 1.9
A technician sets up a signal meter in a corridor.
A signal survey comes before any design or permit.

Your notice

How long do we have?

Every date here comes from the statute or rule cited under it.

In Florida, after the fire marshal issues a notice of code violation, the owner gets at least 1 year to complete a required retrofit. The date written on your notice controls; it may give you more. F.S. 633.202(18)(g)

Codes and standards referenced

Code or standardEditionSource
Florida Fire Prevention Code (NFPA 1 and NFPA 101, Florida editions), in force statewide8th edition (NFPA 1, Florida 2021 edition), effective December 31, 2023rule
Florida Building Code, Broward County Edition, Chapter 1, Section 118Not published; confirm with the fire marshalbora

Notes

We will add Hollywood's own rules when the city publishes them.

Next step

Take the board a plan, not just a problem

Ask for up to 3 quotes from vetted installers who serve your area, or start with a one-page brief the board can read before the next meeting. Free for owners, boards and managers. No texts, no cold calls.

Questions people ask

Does Hollywood publish its own BDA signal requirements?

Not that we could find on the city website as of our last check. Call Fire Prevention and Life Safety at 954.967.4404 and ask which signal levels and test method it uses.

Is Hollywood actually citing buildings?

Yes. A November 2025 Sun-Sentinel report counted 18 of the city's 83 high-rises cited for weak emergency radio coverage.

Sources

Primary documents we read for this page. Rules change; confirm with your fire marshal (AHJ).

  1. Florida Statutes 2026, section 633.202, subsection (18), The Florida SenateVerified October 25, 2026 · statute
  2. Florida Fire Prevention Code, 8th edition: Florida amendments to NFPA 1 (2021 edition), sections 11.10.2 and 11.10.2.1, Florida Division of State Fire MarshalVerified October 25, 2026 · code
  3. Rule 69A-60.003, F.A.C.: NFPA 1, the Fire Code, Florida 2021 edition, adopted (effective 12/31/2023), Florida Department of State, Florida Administrative CodeVerified October 25, 2026 · rule
  4. Fire Prevention and Life Safety: inspections and permitting, City of Hollywood Fire Rescue and Beach SafetyVerified October 25, 2026 · ahj page
  5. BORA ERCES Guidelines, revised 2021-10-14 (archived copy; broward.org blocks automated access), Broward County Board of Rules and AppealsVerified October 25, 2026 · ahj document
  6. Fort Lauderdale cites 69 high-rises with weak radio signals (South Florida Sun-Sentinel via Firehouse, November 2025), Firehouse / South Florida Sun-SentinelVerified October 25, 2026 · news
Get up to 3 quotesCheck this building