Florida · county · ERRCS / BDA requirements

ERRCS and BDA requirements in Hillsborough County, Florida

Hillsborough County Fire Rescue's Fire Marshal's Office is the fire AHJ for unincorporated Hillsborough County. Its published forms and contractor guide do not set BDA signal levels or test steps, so the state rules are the published baseline.

Last verified Updated Confidence low5 sourcesChangelog

Waterfront mid-rise buildings on a Gulf-coast bay.

Confidence low

Last verified

Check this building

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with Hillsborough County Fire Rescue, Fire Marshal's Office before you design, permit or test a system.

Who must comply

State rules apply here too. See Florida statewide rules.

TriggerPublished value
Minimum building sizeNot published; confirm with the fire marshal
Minimum storiesNot published; confirm with the fire marshal
Height triggerNot published; confirm with the fire marshal
Below-grade areasNot published; confirm with the fire marshal
Building types namedNot published; confirm with the fire marshal
Existing buildings must retrofitNot published; confirm with the fire marshal
Compliance deadlineNot published; confirm with the fire marshal

Tampa, Temple Terrace and Plant City have their own fire departments. See the Tampa page.

questions, about a minute

Free. Runs in your browser; nothing is sent until you ask for quotes. The full checker asks a few more questions.

Signal and coverage

Not published by the county.

RequirementValue
Minimum downlink signalNot published; confirm with the fire marshal
Minimum uplink signalNot published; confirm with the fire marshal
Delivered audio quality (DAQ)Not published; confirm with the fire marshal
Coverage, general areasNot published; confirm with the fire marshal
Coverage, critical areasNot published; confirm with the fire marshal
Critical areas namedNot published; confirm with the fire marshal
Public safety radio bandsNot published; confirm with the fire marshal

Not published by the county.

A condominium parking garage with concrete columns and a ramp.
Below-grade garages are where outside radio signal fades first.

How coverage is tested

One floor, 20 squares, a radio check in each

Illustration
The coverage test grid on one floorA floor plan divided into 20 equal test areas in a 5 by 4 grid, with a test spot at the center of each. The stair and the elevator lobby are marked as critical areas. Nineteen areas pass and one fails, so this floor passes.StairElevators1234
  1. 20 test areas per floorEach floor is divided into a grid of 20 roughly equal areas.IFC 2021 510.5.4
  2. One test spot per areaA spot near the center stands for the whole area. No extra spots after it is chosen.
  3. One failed area is allowedMore than one failed area fails the floor. With exactly two, the floor may be re-divided into 40 areas, and up to two non-adjacent failures are allowed.IFC 2021 510.5.4
  4. Critical areas count moreTypical model-code targets: 95 percent of all areas and 99 percent of critical areas such as stairs and elevator lobbies. Your fire marshal sets the numbers that apply to you.IFC 2021 510.4.1

Illustration: 19 of 20 areas pass, so this floor passes. Some fire departments use other numbers; Miami-Dade, for example, stops an acceptance test below 90 percent of general areas.

How the model fire code's grid test decides whether a floor has enough radio coverage.Source: IFC 2021 510.4.1, 510.5.4. Typical model-code values; your AHJ sets them.

Testing

TestWhat the source saysSource
Acceptance testNot published in the local documents we found; confirm with the fire marshal.None found
Annual testNot published in the local documents we found; confirm with the fire marshal.None found
Five-year testNot published in the local documents we found; confirm with the fire marshal.None found
Coverage assessment intervalSet by state law: the fire marshal may require an interior coverage assessment no more than once every 3 years for an existing high-rise or an existing building over 12,000 total gross square feet, and once every 5 years for other existing buildings, with exceptions for major alterations, reported radio failures and imminent threats.F.S. 633.202(18)(c)2
A firefighter keys a shoulder microphone in a stairwell.
Testers check talk-in and talk-out from stairwells and other critical areas.

Permit and inspection process

  1. Call the Fire Marshal's Office at (813) 744-5541 and ask how it tests radio coverage and permits BDA systems. Inspections are called in before 3 PM. Fire Marshal's Office page
  2. Fire Marshal plan review and acceptance test request forms are on the county's applications page. Applications and forms
A technician sets up a signal meter in a corridor.
A signal survey comes before any design or permit.

Your notice

How long do we have?

Every date here comes from the statute or rule cited under it.

In Florida, after the fire marshal issues a notice of code violation, the owner gets at least 1 year to complete a required retrofit. The date written on your notice controls; it may give you more. F.S. 633.202(18)(g)

Codes and standards referenced

Code or standardEditionSource
Florida Fire Prevention Code (NFPA 1 and NFPA 101, Florida editions), in force statewide8th edition (NFPA 1, Florida 2021 edition), effective December 31, 2023rule

Notes

We will add the county's own rules when it publishes them.

Next step

Take the board a plan, not just a problem

Ask for up to 3 quotes from vetted installers who serve your area, or start with a one-page brief the board can read before the next meeting. Free for owners, boards and managers. No texts, no cold calls.

Questions people ask

Does Hillsborough County publish BDA signal requirements?

Not in the Fire Marshal forms and contractor guide we reviewed. Call the Fire Marshal's Office at (813) 744-5541.

Is the county fire marshal the AHJ for a building in Tampa?

No. Inside Tampa city limits, Tampa Fire Rescue's Fire Marshal's Office is the AHJ.

Sources

Primary documents we read for this page. Rules change; confirm with your fire marshal (AHJ).

  1. Florida Statutes 2026, section 633.202, subsection (18), The Florida SenateVerified October 25, 2026 · statute
  2. Florida Fire Prevention Code, 8th edition: Florida amendments to NFPA 1 (2021 edition), sections 11.10.2 and 11.10.2.1, Florida Division of State Fire MarshalVerified October 25, 2026 · code
  3. Rule 69A-60.003, F.A.C.: NFPA 1, the Fire Code, Florida 2021 edition, adopted (effective 12/31/2023), Florida Department of State, Florida Administrative CodeVerified October 25, 2026 · rule
  4. Fire Marshal's Office, Hillsborough County Fire RescueVerified October 25, 2026 · ahj page
  5. Fire Marshal permits: applications and forms, Hillsborough CountyVerified October 25, 2026 · ahj page
Get up to 3 quotesCheck this building