Florida · city · ERRCS / BDA requirements
ERRCS and BDA requirements in Boca Raton, Florida
Boca Raton Fire Rescue's Fire and Life Safety Division inspects buildings and reviews plans in the city. We found no BDA signal levels or test procedures published by the city, so the state rules are the published baseline.

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with Boca Raton Fire Rescue Services, Fire and Life Safety Division before you design, permit or test a system.
Who must comply
State rules apply here too. See Florida statewide rules.
| Trigger | Published value |
|---|---|
| Minimum building size | Not published; confirm with the fire marshal |
| Minimum stories | Not published; confirm with the fire marshal |
| Height trigger | Not published; confirm with the fire marshal |
| Below-grade areas | Not published; confirm with the fire marshal |
| Building types named | Not published; confirm with the fire marshal |
| Existing buildings must retrofit | Not published; confirm with the fire marshal |
| Compliance deadline | Not published; confirm with the fire marshal |
Boca Raton is a separate fire AHJ from Palm Beach County Fire Rescue. Ask the division which signal level it tests to.
Signal and coverage
Not published by the city.
| Requirement | Value |
|---|---|
| Minimum downlink signal | Not published; confirm with the fire marshal |
| Minimum uplink signal | Not published; confirm with the fire marshal |
| Delivered audio quality (DAQ) | Not published; confirm with the fire marshal |
| Coverage, general areas | Not published; confirm with the fire marshal |
| Coverage, critical areas | Not published; confirm with the fire marshal |
| Critical areas named | Not published; confirm with the fire marshal |
| Public safety radio bands | Not published; confirm with the fire marshal |
Not published by the city.

How coverage is tested
One floor, 20 squares, a radio check in each
- 20 test areas per floorEach floor is divided into a grid of 20 roughly equal areas.IFC 2021 510.5.4
- One test spot per areaA spot near the center stands for the whole area. No extra spots after it is chosen.
- One failed area is allowedMore than one failed area fails the floor. With exactly two, the floor may be re-divided into 40 areas, and up to two non-adjacent failures are allowed.IFC 2021 510.5.4
- Critical areas count moreTypical model-code targets: 95 percent of all areas and 99 percent of critical areas such as stairs and elevator lobbies. Your fire marshal sets the numbers that apply to you.IFC 2021 510.4.1
Illustration: 19 of 20 areas pass, so this floor passes. Some fire departments use other numbers; Miami-Dade, for example, stops an acceptance test below 90 percent of general areas.
Testing
| Test | What the source says | Source |
|---|---|---|
| Acceptance test | Not published in the local documents we found; confirm with the fire marshal. | None found |
| Annual test | Not published in the local documents we found; confirm with the fire marshal. | None found |
| Five-year test | Not published in the local documents we found; confirm with the fire marshal. | None found |
| Coverage assessment interval | Set by state law: the fire marshal may require an interior coverage assessment no more than once every 3 years for an existing high-rise or an existing building over 12,000 total gross square feet, and once every 5 years for other existing buildings, with exceptions for major alterations, reported radio failures and imminent threats. | F.S. 633.202(18)(c)2 |

Permit and inspection process
- Call the Fire and Life Safety Division (561-982-4000) and ask how to request a radio coverage test and submit BDA plans. Fire and Life Safety page

Your notice
How long do we have?
Every date here comes from the statute or rule cited under it.
In Florida, after the fire marshal issues a notice of code violation, the owner gets at least 1 year to complete a required retrofit. The date written on your notice controls; it may give you more. F.S. 633.202(18)(g)
Codes and standards referenced
| Code or standard | Edition | Source |
|---|---|---|
| Florida Fire Prevention Code (NFPA 1 and NFPA 101, Florida editions), in force statewide | 8th edition (NFPA 1, Florida 2021 edition), effective December 31, 2023 | rule |
Notes
We will add the city's own rules when it publishes them.
Next step
Take the board a plan, not just a problem
Ask for up to 3 quotes from vetted installers who serve your area, or start with a one-page brief the board can read before the next meeting. Free for owners, boards and managers. No texts, no cold calls.
Questions people ask
Who decides whether a Boca Raton building needs a BDA?
The city's Fire and Life Safety Division, as the local fire AHJ, using the state rules in F.S. 633.202(18).
Does Boca Raton publish its own BDA signal levels?
Not that we could find as of our last check. Ask the division at 561-982-4000.
Sources
Primary documents we read for this page. Rules change; confirm with your fire marshal (AHJ).
- Florida Statutes 2026, section 633.202, subsection (18), The Florida Senate
- Florida Fire Prevention Code, 8th edition: Florida amendments to NFPA 1 (2021 edition), sections 11.10.2 and 11.10.2.1, Florida Division of State Fire Marshal
- Rule 69A-60.003, F.A.C.: NFPA 1, the Fire Code, Florida 2021 edition, adopted (effective 12/31/2023), Florida Department of State, Florida Administrative Code
- Fire and Life Safety Division, City of Boca Raton Fire Rescue Services