California · city · ERRCS / BDA requirements

ERRCS and BDA requirements in Palo Alto, California

Palo Alto requires radio coverage in new buildings where the fire code official requires it and measured signal falls below the city's levels for the SVRIA 700 MHz P25 system. Existing buildings follow California Fire Code Chapter 11, and every existing system must be upgraded to cover 700 through 800 MHz at the owner's expense.

Last verified Updated Confidence medium2 sourcesChangelog

Mid-rise and high-rise buildings from street level.

Confidence medium

Last verified

Check this building

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with Palo Alto Fire Department, Fire Prevention Bureau before you design, permit or test a system.

Who must comply

State rules apply here too. See California statewide rules.

RuleEffectCitationSource
New buildings must have approved radio coverage where the fire code official requires it and signal strength is below the levels in Section 510.4.1. Buildings that already meet the SVRIA signal levels without a system are excepted.AHJ may requirePAFD 510.1 and Exception 4City of Palo Alto Fire Department, Fire Prevention Bureau
Existing buildings must provide coverage as required in California Fire Code Chapter 11. All existing systems must be upgraded to cover 700 through 800 MHz at the owner's expense.NotePAFD 510.2City of Palo Alto Fire Department, Fire Prevention Bureau
TriggerPublished value
Minimum building sizeNot published; confirm with the fire marshal
Minimum storiesNot published; confirm with the fire marshal
Height triggerNot published; confirm with the fire marshal
Below-grade areasNot published; confirm with the fire marshal
Building types namedNot published; confirm with the fire marshal
Existing buildings must retrofitYes
Compliance deadlineNot published; confirm with the fire marshal

The standard is Rev. 06/25/2020 and cites the 2019 California codes. Newer code editions may change the details.

questions, about a minute

Free. Runs in your browser; nothing is sent until you ask for quotes. The full checker asks a few more questions.

RequirementValue
Minimum downlink signal-95 dBm
Minimum uplink signal-95 dBm
Delivered audio quality (DAQ)3.4
Coverage, general areas95% of floor area
Coverage, critical areas99% of floor area
Critical areas namedFire command centers, Fire pump rooms, Interior exit stairways, Exit passageways, Elevator lobbies, Standpipe cabinets, Rescue air filling stations, Sprinkler sectional valve locations, Restrooms, Other areas the fire code official requires
Public safety radio bandsSVRIA P25 Phase 2 700 MHz digital trunked radio system

Inbound: at least -95 dBm in 95% of each floor from the SVRIA system. Outbound: -95 dBm received at the donor site from 95% of each floor. A 20 dB difference between interior and exterior signal is required. Only FCC-certified Class A channelized public safety BDA/DAS equipment is allowed, and the ERRCS may not be combined with other DAS. Cabling needs a 2-hour fire-resistive rating and mechanical protection.

A firefighter keys a shoulder microphone in a stairwell.
Coverage is measured where firefighters work: stairwells, corridors and below grade.

How coverage is tested

One floor, 20 squares, a radio check in each

Illustration
The coverage test grid on one floorA floor plan divided into 20 equal test areas in a 5 by 4 grid, with a test spot at the center of each. The stair and the elevator lobby are marked as critical areas. Nineteen areas pass and one fails, so this floor passes.StairElevators1234
  1. 20 test areas per floorEach floor is divided into a grid of 20 roughly equal areas.IFC 2021 510.5.4
  2. One test spot per areaA spot near the center stands for the whole area. No extra spots after it is chosen.
  3. One failed area is allowedMore than one failed area fails the floor. With exactly two, the floor may be re-divided into 40 areas, and up to two non-adjacent failures are allowed.IFC 2021 510.5.4
  4. Critical areas count moreTypical model-code targets: 95 percent of all areas and 99 percent of critical areas such as stairs and elevator lobbies. Your fire marshal sets the numbers that apply to you.IFC 2021 510.4.1

Illustration: 19 of 20 areas pass, so this floor passes. Some fire departments use other numbers; Miami-Dade, for example, stops an acceptance test below 90 percent of general areas.

How the model fire code's grid test decides whether a floor has enough radio coverage.Source: IFC 2021 510.4.1, 510.5.4. Typical model-code values; your AHJ sets them.

Testing

TestWhat the source saysSource
Acceptance testEach floor is divided into 20 test areas; the test passes when 95% of test locations pass two-way talk-back on the SVRIA system (99% in critical areas). A third-party consultant reviews plans before the fire permit and submits the acceptance report before final inspection. All results must be validated by an approved third party independent of the designer and installer.PAFD 510.5.3; 3rd party requirements
Annual testThe system must be inspected and tested every year and after structural changes, at the owner's expense. Tests include the coverage test, BDA gain check, a 1-hour battery load test and component checks, validated by an independent third party, with a report to the fire code official.PAFD 510.6.1
Five-year testNot published in the documents we read; confirm with the fire marshal.None found
Coverage assessment intervalNot published in the documents we read; confirm with the fire marshal.None found
An amplifier enclosure and battery cabinet in an equipment closet.
The amplifier, its battery and its alarms are part of every acceptance and annual test.

Maintenance and monitoring

  • Systems out of service for more than 8 hours require notification to the fire code official.
  • A UPS must run the ERRCS for at least 24 hours; an emergency power-off switch is required.
  • Signs: 'Radio System Installed' near the key box and 'ERRCS' on the equipment room door, per the city sign standard.

Source: PAFD Section 510 - ERRCS Codes and Addendums, Palo Alto Emergency Responder Radio System Guidelines (Rev. 06/25/2020)

Permit and inspection process

  1. Register the system with the Silicon Valley Regional Interoperability Authority (SVRIA) and submit proof with the plans. PAFD 510.3.1
  2. Have a third-party consultant review the plans and issue a letter of acceptance before the fire permit submittal. PAFD, 3rd party requirements
  3. Get a construction permit; a frequency change on an existing system needs a new fire permit. PAFD 510.3
  4. Before final inspection, the same consultant submits an acceptance report with a 20-grid-per-floor test and an uplink test. PAFD, 3rd party requirements
A technician and a manager review a building drawing.
Most fire departments review drawings before an installer can start.

Codes and standards referenced

Code or standardEditionSource
California Fire Code Section 510 and 1103; California Building Code Section 9172019 (named in the standard)s1
NFPA 1221Not published; confirm with the fire marshals1

Notes

Medium confidence: the standard is from 2020. We read it through an Internet Archive copy because the city site blocks automated requests; the live link is listed first.

Next step

Take the board a plan, not just a problem

Ask for up to 3 quotes from vetted installers who serve your area, or start with a one-page brief the board can read before the next meeting. Free for owners, boards and managers. No texts, no cold calls.

Questions people ask

Who must validate ERRCS test results in Palo Alto?

An approved third party independent of the system designer and installer, for both acceptance and annual tests (PAFD 510.5.3 item 8 and 510.6.1).